| Technical
Specifications - 8310 Series |
Model No. UPS Rating
/ Capacity |
OSOL10000 |
OSOL15000 |
OSOL20000 |
OSOL30000 |
| 10
KVA |
15 KVA |
20 KVA |
30 KVA |
| 8
KW |
12
KW |
16
KW |
24
KW |
| Operating
Mode & Principle |
True
On-Line, Double Conversion, Input & Output Galvanic
Isolation |
| Technology |
PWM
/ IGBT |
| INPUT |
| Phase |
3
Phase + N + G |
| Voltage |
380V
+ 25% |
| Frequency |
50
Hz + 5Hz |
| P. F. |
0.92
P.F. |
| Bypass
Input |
| Phase |
3
Phase + N + G |
| Voltage |
380
V + 25% |
| Frequency |
50
Hz + 5Hz |
| Transfer Time |
0ms.
Inverter to Bypass (Over Load) |
| DC
System |
| DC Voltage |
360
V DC |
| Charging
Current |
1Amp
– 30Amp (Adjustable) |
| OUTPUT |
| Phase |
Single
Phase |
| Voltage |
230V
+ 1% |
| Frequency |
50
Hz + 0.5Hz |
| Waveform |
Pure
Sine Wave |
| P. F. |
0.8 |
| Distortion |
<
3% (On-Liner Load), < 5% (On Non-Liner Load) |
| Transient |
<
10ms. |
| Over
Load |
125%
for 1 Min. |
| |
150%
for 1second |
| Cooling |
Forced
Air Cooled |
| PROTECTION |
| General |
Output
Over Load, Short Circuit, Over Temp., Battery Low
& Over Charge |
| Audible
Alarm |
Mains
Fail, Load On Battery, Inverter Fault |
| SYSTEM |
| Over
All Efficiency |
91% |
92% |
| Communication |
RS-232
Port OR SNMP (Optional) |
| Temperature |
0O
C To 40O C |
| Humidity |
30
To 90% |
| Noise (db) |
40
– 60 db |
|
|
|
|
|